- 8 channels
- 4 objects per channel
- OnOff
- Info OnOff
- Feedback object, i.e. it sends information to the bus
- Intrusion Alarm
- Switches on the lamp and makes it flash while the alarm is triggered
- The channel (lamp) cannot not be controlled via the other objects as long the alarm is triggered
- Fire Alarm
- Switches on the lamp after the alarm has been triggered
- The channel (lamp) cannot not be controlled via the other objects as long the alarm is triggered
- About the alarms:
- Fire has higher priority than Intrusion
- triggered alarms are indicated in the channel labels: as 'F' in case of fire and 'I' in case of intrusion
- 1 parameter per channel: staircase timeout
- no timeout
- 3/10 seconds
- staircase timers are while not elapsed indicated in the channel labels as 'T'
- device commission parameter (master reset), i.e. an 'application download' affects either:
- the objects values of all channels
- the object values of one specific channel
- none of the object values