ETS6 project file
- Attached at the bottom of the page
Project password:
a
Required devices
- D4 - KliX
- D5 - TP/TP Coupler
- D6 - Valve Actuator
- D10 - Movement/Presence Detector
- D11 - Binary Input (reed switches)
- D12 - Weather Module
- D15 - Setpoint Manager
- D16 - Heat Controller
- D17 - Heat Exchanger
Links
- Outside temperature between D4 & D12
- Window status between D11.1 & D15
- Presence status between D10.1 & D15
- Room temperature between D4 & D16
- Heat/Cool status between D17 & D16
- The 'User' objects (3) between D4 & D15
- The 'Effective' objects (3) between D15 & D16
- The 'Actual' objects (3) between D16 & D4
- The 'Valve' objects (2) between D16 & D6 (room1)
- D4.4 (2 toggle objects) disables/enables D11.1 & D10.1
Tests :
1. Set :
- Window status to 'open'
- Outside temperature to 0 °C
- Expected result :
- SP will be set to 8 °C
- The label of D16.1 is colored red : to indicate 'frost protection mode'
2. Set :
- Window status to 'open'
- Outside temperature to 35 °C
- Expected result :
- SP will be set to 30 °C
- The label of D16.1 is colored blue : to indicate 'overheating protection mode'
3. Set :
- Window status to 'close'
- Presence status to 'not occupied'
- Outside temperature to 0 °C
- Expected result : SP will be set between 17 and 19 °C
4. Set :
- Window status to 'close'
- Presence status to 'not occupied'
- Outside temperature to 35 °C
- Expected result : SP will be set between 25 and 27 °C
5. Set :
- Window status to 'close'
- Presence status to 'occupied'
- Outside temperature to 0 °C
- Expected result : SP can be set to :
- 'standby', i.e. between 17 and 19 °C
- 'comfort', i.e. between 21 and 23 °C
6. Set :
- Window status to 'close'
- Presence status to 'occupied'
- Outside temperature to 35 °C
- Expected result : SP can be set to :
- 'standby', i.e. between 25 and 27 °C
- 'comfort', i.e. between 21 and 23 °C
7. Dead band (heat)
- Set window closed to 'close'
- Set presence status to 'occupied'
- Make sure that the heat/cool status of D17 is set to heat (red text)
- Set outside temperature to 22 °C
- Set SP to 21 °C
- D17 is not able to cool, i.e. the SP will not be reached
8. Dead band (cool)
- Set window closed to 'close'
- Set presence status to 'occupied'
- Make sure that the heat/cool status of D17 is set to cool (blue text)
- Set outside temperature to 22 °C
- Set SP to 23 °C
- D17 is not able to warm, i.e. the SP will not be reached