Problem
ETS does not start or other error messages similar to the one below are shown:
2023-04-03 14:48:02,961 [1] ERROR System.Windows.Application - System.ArgumentNullException: Der Wert darf nicht NULL sein.Parametername: keybei System.Collections.Generic.Dictionary`2.Insert(TKey key, TValue value, Boolean add)bei System.Linq.Enumerable.ToDictionary[TSource,TKey,TElement](IEnumerable`1 source, Func`2 keySelector, Func`2 elementSelector, IEqualityComparer`1 comparer)bei System.Linq.Enumerable.ToDictionary[TSource,TKey,TElement](IEnumerable`1 source, Func`2 keySelector, Func`2 elementSelector)bei Knx.Ets.ObjectModel.Operations.GroupRanges.DeleteGroupRangeOperation..ctor(IEnumerable`1 ranges, Action`1 progress)bei Knx.Ets.ViewModel.Application.Workspace.OperationFactory.CreateDeleteOperation(IEnumerable`1 items, Action`1 callback)bei Knx.Ets.ViewModel.ContextMenu.ContextMenuViewModel.<>c__DisplayClass163_0.<OnDelete>b__0(Action`1 action)bei Knx.Ets.ViewModel.Application.Wizards.GenericWizardPageVM..ctor(String wizardId, Func`2 getOperations, Func`2 getSubtitle, WizardPageAttachment attachment)bei Knx.Ets.ViewModel.Application.Wizards.GenericWizardViewModel..ctor(IList`1 objects)bei Knx.Ets.ViewModel.IocModule.<>c.<Load>b__0_39(Object[] objects)bei Knx.Ets.ViewModel.Tools.WizardDialogService.GetWizard(Object[] values)bei Knx.Ets.ViewModel.Tools.WizardDialogService.ShowGeneric(Boolean withDelay, Object[] values)bei Knx.Ets.ViewModel.Service.ProgressDialogService.ShowDialog(WizardSubtype wizardSubtype, Func`2 getOperationsWithCallback, Action`1 whenFinishedCallback, String localizedDescription, Boolean useDelay)bei Knx.Ets.ViewModel.ContextMenu.ContextMenuViewModel.OnDelete()
Cause
The workspace configuration file is damaged and ETS cannot process it.
Solution
- Close ETS (if it's open).
- Locate the project's folder in the project store folder.
- Note down the project's folder name (i.e. P-ABCD, where ABCD is the project ID).
- Browse to the folder '%localappdata%\KNX\ETS5\Workspaces' (copy the content within the ' ' to Windows File Explorer).
- Find and delete the file 'P-ABCD.workspace', where P-ABCD is the project's ID.
- Start ETS again.