General
Option | Description |
Timestamp format | Format of the Time column in the monitor. Possible values are Time only (hh:mm:ss.ms) and Date and time (yyyy-mm-dd hh:mm:ss.ms). |
Maximum number of telegrams displayed during recording | Number of telegrams shown in the window. If the number indicated here is exceeded, older telegrams will be deleted from the window. Is not used when the telegrams are loaded from a file. A setting with a value < 100 is not possible. |
Warn if closing telegram monitor containing unsaved telegrams | A warning is issued when closing if this will cause unsaved telegrams to be lost. |
Capture filter condition |
The "point" at which the monitor begins recording telegrams depends on this (pre- or user-defined) condition. Telegrams that do not meet the condition will be ignored. |
Use filter condition when loading from file | If selected, the filter conditions are also applied when telegrams are loaded from a file (to reduce the amount of content displayed). |
Capture trigger condition |
The "point" at which the monitor begins displaying telegrams depends on this (pre- or user-defined) condition. Telegrams that do not meet the condition will be ignored. To process a telegram here it must have first met the Capture filter condition! |
Number of telegrams to be displayed before the trigger point |
The number of telegrams before the trigger point is set using this option. |
Number of telegrams to be displayed after the trigger point |
Use this option (and the previously enabled option þ Limit ... ) to limit the number of telegrams after the trigger point. |
Use trigger condition when loading from file |
If selected, the capture trigger conditions are also applied when loading telegrams from a file (to reduce the amount of content displayed). |