Both ETS Monitors show the information about the recorded telegrams in tabular form. Most of the information is explained in the Bus Monitor & Group Monitor. Below, you can find detailed explanations to the control information of the window columns 'Flags' and 'Destination address'.
Window columns
Flags |
Control Information: Flags shown in the bus monitor are marked with BM
- E: Frame Format (Extended Frame)
- H: Frame Format (LTE-HEE Frame)
- R: Repetition
- a: Acknowledge expected
- C: Confirmation Flag, set if Acknowledge is negative
- F: BM; Frame Stop Bit Error
- B: BM; Data Bit Error
- P: BM; Parity Bit Error
- O: BM; Overflow
- L: BM; Telegram lost
- S: BM; sequence counter, x=0-7
|
Destination address |
The following variants can occur, depending on the telegram 'type'
- For P2P connectionless / connection-oriented communication > Display of the Individual Address
- For group communication > Display of the Group Address, always in the respective coding of the Group Address structure
- For (system) broadcast communication > Display of the Group Address (with the value 0), always in the respective coding of the Group Address structure (e.g. 0/0/0)
- For LTE (Logical Tag Extended) group communication > Display of the LTE zones information according to the KNX specification, e.g. Geographical, Application Specific, General Peripheral
|